Guide to Solar Water Heater Installation Best Practices Bob Ramlow In my work with many solar water heating manufacturers, designers and installers here in the upper Midwest I have compiled a list of best installation practices for solar water heating systems. This work is collaboration and is ongoing, so if you have anything to add to this work, please send me your additions. I live in Wisconsin, and the climate is harsh for solar water heating systems. Temperatures can reach well over 1000 F during the summer and fall to -300F or colder during the winter. I have also seen the temperature drop over 400F in less than a day. This is a tough environment for a solar water heating system to survive in. But, if a solar water heating system can survive here in Central Wisconsin, it can survive anywhere. As is often the case, the devil is in the details, and when designing a solar water heating system it is imperative to get all of the details correct if we want a quality installation. Details are what we cover in this compilation. Of course the installation begins with the sale, so that is where we’ll start. Introduction to Solar Water Heater Installation Best Practices This manual was developed as a tool to assist solar thermal designers and installers as a guideline to provide the most reliable solar hot-water systems possible. The material presented here is not intended to be used as a list of system requirements or as a type of solar code. Rather, it was assembled with the input of many parties to share lessons learned in the field. It is not inclusive and it is a work in progress. Some areas in Wisconsin have over 10,000 heating degree days, where winter temperatures regularly fall below -30°F. In fact, the record coldest temperature recorded in Wisconsin was -55°F. During the summer, temperatures can rise above 100°F. While most climates are not this severe, the practices outlined in this manual will be helpful for system designs in all cold climates as well as in warm climates. A properly designed solar hot-water system must not only function properly during extreme cold and hot environmental circumstances, it must also be able to safely endure sustained periods of low or no hot water draw without damage or overheating. A best practice is defined as: A practice that is most appropriate under the circumstances. A technique or methodology that, through experience and research, has reliably led to a desired or optimum result. Overview: A well-designed solar water heating system that is appropriate for the climate where it is located, and is properly installed (with appropriate solar rated components) will last for many years. Being a mechanical system, some components will eventually wear out and fail. The typical wear parts in a solar water heating system include the pumps, the expansion tank, automatic valves and the solar fluid. Environmentally, lightening can damage the controller. Studies have been conducted on solar water heating system reliability, but they have been limited by the lack of data available. Despite the lack of data, certain conclusions have been indicated. All mechanical systems follow a common reliability path that identifies when problems typically occur. A “bathtub curve” demonstrates this. The following table comes from a solar water heating reliability report created by Sandia Labs under a grant from the US Department of Energy. This graph shows that the greatest probability of a failure will occur at the startup and at the end of system or component life. The failure rate early in the device’s life is characterized by startup failures due to design flaws, faulty new equipment or components, installation errors, and misuse (the yellow area). Once these initial problems are corrected the device enters its useful operational period where failures are due to chance occurrence (green area). Later, as the device and its components age, the failures begin to increase because the system is wearing out. Failures start to slowly creep in and eventually the system fails (red area). Because most solar collectors and piping systems can last well past the average life of a pump (or other shorter life components), replacing the failed component can bring a failed system back to life. This research shows the importance of post-installation inspection or monitoring to overcome potential startup failure. Solar water heating systems are unique in that it is difficult to notice a system failure. This is because there is always a full-size backup water heating system in place. The owner may not recognize a malfunction because hot water is still running. This situation shows how critically important it is that the solar water heating system be checked periodically. Owner involvement is mandatory and the system owner must be aware of this responsibility before the installation is started. If the owner is not willing to check the system at least monthly, then the sale should not take place… unless a service contract is in place or some type of alarm is installed to alert the owner of a system failure. Installers should conduct follow-up inspections within a reasonably short period of time after the system is commissioned to identify any startup failures. Site Assessment For All System Types: Harnessing the sun’s energy requires proper orientation and location of the solar collectors to maximize system performance, efficiency and ease of installation. A site analysis should be performed before purchasing equipment to ensure there is access to the southern sky. This equipment should be placed in an area without excessive shading, and there should be plenty of available space for the installation of the solar collectors, solar storage and drainback tanks, pumps or integrated pump stations and associated piping. Steps for an effective site analysis: Determine the load: The proposed location must have access to the southern sky with a minimum amount of shading between 9:00 AM and 3:00 PM each day throughout the year. The solar collectors should be located as close to the solar storage tank as possible to minimize heat loss in the piping runs, pump power and reduce installation cost. Placing the collectors as close as possible to the peak, with no less than 3 feet available for maintenance clearance, (on pitched roofs) will make installation easier by providing increased attic access. Placing the collectors near the edge of the roof will make installation difficult since attic access is more restricted at this point. The attic space must be examined during the site analysis to confirm adequate space is available for installing the solar collectors in the proposed location. Be aware that the top 6 feet on the South side of the peak is known as the snow surcharge area (drifting). The best vertical orientation for year-round applications is achieved when the collectors are tilted at an angle equal to the geographic latitude of the location. Tilt kits are available to achieve the optimal vertical angle. NOTE: Customers often prefer to have the solar collectors flush mounted to the roof for aesthetic reasons. Modern solar collectors are efficient enough that flush mounting to pitched roofs will still provide reasonable performance for domestic water heating. Therefore, customer’s preferences should always be considered. The best horizontal orientation is achieved when the collectors are facing due south plus or minus 30° — this is often referred to as the azimuth angle. A south facing location for the collectors is ideal. A north facing location will not provide adequate access to the sun’s energy and are not suitable for locating the solar collectors. East and west facing roof locations may be used but will require tilt kits to orient the collectors towards the southern sky. Web sites with satellite imagery (such as Google Maps) can often be used to survey the orientation of the roof before a site visit. Make sure the client understands what solar hot-water systems can and cannot do. Many potential system owners are enthusiastic about the prospect of owning a solar hot-water system but may not really understand the characteristics or limitations of this type of investment. Try to have all decision makers present during the site assessment or the sales call. Most residential clients have no idea how much hot water they actually use; where feasible, meter the hot water load for a month. Otherwise, do a load profile based on the ANSI/ASHRAE 90.2-2007 formula: AGPD = [CW + SPA + B](NP) Where: AGPD = average gallons per day of hot water consumption CW = 2.0 gal/day per person if a clothes washer is present in living unit, otherwise zero SPA = 1.25 gal/person per day additional hot water use if a ‘spa-tub is present in living unit, otherwise zero B = 13.2 gal/person NP = number of people in living unit; if exact information is unknown, estimate as follows, where NSR = number of sleeping rooms: (1.0)(NSR) for single-family detached and manufactured (mobile) homes with one to four sleeping rooms, plus (0.5)(NSR) for each sleeping room beyond four, or (1.25)(NSR) for multifamily buildings with one to four sleeping rooms per dwelling unit, plus (0.5)(NSR) for each sleeping room beyond four Inquire whether the energy users of the household may bear any behaviors or activities that will consistently exceed or reduce the estimate based on the ASHRAE guidance. Encourage the replacement of old appliances. Document whether loads are consistent or intermittent by inquiring about vacation patterns or other absences in occupancy throughout the year. On both residential and commercial systems, look for multiple loads that a single system can satisfy. If possible, try to find both winter and summer loads to satisfy so the system can provide heat all year round. Do not install collectors on a bad roof. Learn more about how to spot a “bad roof” here. If shingles are nearing the end of their useful life (curling, breaking, or significant loss of aggregate), the building should be re-roofed before the collectors are installed. Use a site assessment tool to help determine the best place for the collectors: Document the solar window by taking a digital photo of the site assessment tool. Provide a copy to the owner and keep a copy in your files. Collectors can be oriented within 30 degrees of due South with little difference in output. Model system performance: When using computer modeling tools, use the following parameters: When shading occurs within the solar window, it is typically the case that the site’s shading occurs in the winter months. Do not recommend a space-heating component if that is the case. When shading is a concern, note that while nearly all heat is collected during the hours of 9 AM to 3 PM (solar time), a majority of the heat is actually collected between 10 AM to 2 PM. If this window is less than 10% shaded, it is considered a good site for a solar water-heating system. Count branches of a deciduous tree at 50% shaded during the hours impacted if the shading occurs from October to March. Pay attention to future tree growth horizons — recommend to the owner that there should be no trees planted within 50 feet of the site. If options are available, involve the client in deciding which sites are acceptable for collector placement. This will prevent misunderstandings about placement and last-minute changes to the pump size. If the site has very limited solar access, document the reasons for exact collector placement. Don’t recommend a system if the site is more than 35% shaded. While most of the energy collected from any solar thermal system will be in the spring, summer and fall months, you want customers to be satisfied with their investment year-round. In case of summer uses (i.e. cabin, pool), winter shading can be ignored. Document all optional pipe runs from collectors to the balance of the system. Document that there is room for the balance of the system. If walls will be opened, document repair/carpentry costs. Record measurements of stairs or door openings and determine whether they are large enough to allow tank placement. When the site analysis is complete, and it has been confirmed that the proposed location will provide adequate access to the sun and room to install, the equipment sizing and equipment selection can be made. Ensure the local codes regarding all mechanical components, particularly single wall or double wall heat exchanger requirements are understood before equipment is purchased. Order double wall heat exchanger systems if required by local codes. Typically, propylene glycol systems don’t require double-wall heat exchanger (verify with local code official). Ethylene glycol systems always require a double-wall heat exchanger to potable water. Typical system design Undersize rather than oversize: Size the system to provide a maximum of 100% on best solar day. This sizing scheme results in systems that do not overheat as well as systems that have the highest possible return on investment (ROI). Specify appropriate system type: Consider drainback systems for intermittent loads or seasonal load types, if practical. Consider pressurized glycol systems for systems that have pipe runs that cannot maintain a ¼” per foot slope back to the drainback tank and for ground mounted systems. Typically, the area available for the collector array will determine the size of system, especially in commercial applications. Another space limitation, particularly for commercial installations, is the available room for the solar storage tanks and the balance of system components in the mechanical room. If collector arrays will be in a saw tooth configuration, make sure the southern array will not shade the northern array. Note: A little shading when the sun is at its lowest angle will not seriously impact the performance of the system. Systems that serve multiple loads typically have a better return on investment than single load applications. Plan installation carefully so you have all components on site. Residential system design System sizing: In order to qualify for the current federal tax credit, a residential system must be sized to cover half of the household’s domestic hot water load. This is the ideal maximum for solar hot-water systems without space or pool heating. Space Heat: This option is very popular in cold climates. The collectors should be tilted to maximize the winter sun (location latitude plus 150). To minimize potential summer overheating, consider including a heat diversion circuit to dissipate unwanted heat when necessary, or recommend a drainback system. Aesthetics: Many potential solar hot-water system owners would prefer that the collectors be flush mounted (parallel to the roof). While this practice will have only a small impact on the performance of the solar hot-water system in most climates, it is important that the prospective owner be aware that in a climate that experiences both a significant amount of annual snowfall plus prolonged below freezing temperatures, there will be a reduction in overall system performance if the collectors are not tilted to an angle of at least 450. Production will be lost during the winter when daily production is at it’s lowest. If the owner of a large house wants a solar hot-water system, but currently there are only 1-2 occupants, system sizing will depend on the future intentions of the owner. If the plan is to have children or to sell the home in the next few years, size the system slightly large and consider the following: 1) Tilt the collectors to the winter angle. 2) Oversize the storage tank. Two-tank systems outperform one-tank systems in climates that experience extended cloudy periods. All systems require a listed Thermostatic Mixing Valve (TMV) at the exit hot water outlet of the back-up heater. If the back-up heater is on-demand, the TMV may be installed between the solar storage tank and the on-demand heater. Check with the water heater manufacturer to determine the maximum incoming water temperature allowed; and if necessary install the TMV between the storage tank and the on-demand heater. Set the TMV at or below this temperature. If the back-up water heater is an on-demand type, be sure that the on-demand heater will modulate to the “off” position if the incoming preheated water is already up to temperature. Non-residential system design Never install an automatic water fill valve on pressurized glycol systems. It is acceptable to use a glycol fill system (injection pump) that injects a pre-mix of glycol into the solar loop if the pressure drops in that loop (sometimes called a glycol makeup system.) Size the Heat Exchanger (HX) for the worst-case scenario, with maximum possible water temperature and solar fluid temperature. To accommodate this worst case, the HX cannot be too big. Install Pressure Relief Valve (PRV) in the mechanical room: Pipe the PRV to within 6” of the floor. Locate the PRV between the collectors and any isolation valves in the system. Size the PRV appropriately in relation to the maximum BTU output of the system. Components Maximum flow rates for copper tubing: Size the piping to maintain 5 feet of water column (head) per 100 feet of pipe. The following graph also shows the amount of heat that can be pushed through a pipe size at the identified flow rates and temperature rise. Pipe Size (in) Flow (gpm) Energy Delivered (BTUH @ 20°F temp rise) ½ 1.5 15,000 ¾ 4 40,000 1 8 80,000 1 ¼ 14 140,000 1 ½ 22 220,000 2 47 470,000 2 1/2 85 850,000 3 130 1,300,000 Another method of pipe sizing is based on fluid velocity (between 2 and 5 feet/second) and head loss. The table below summarizes this method. Pipe Size(in) Flow Rate(gpm) 1/2 1 – 3 ¾ 3 – 7 1 5 – 12 1 ¼ 8 – 19 1 ½ 11 – 28 2 20 – 49 2 ½ 31 – 76 3 44 – 110 4 78 – 296 Sizing with a flow rate greater than 5 feet per second (undersizing the pipe) results in pipe erosion and requires excessive pumping energy. This is important because it differs from the plumbing code. Closed-loop piping with pumps and glycol is different than open-loop piping with water. Sizing less than 2 feet per second (oversizing the pipe) results in excessive costs, the inability to move air through the piping (which is especially critical in drainback systems), and potentially a significant amount of heat loss through the pipe because its residence time is so high. Sizing for head loss is important because it determines the amount of pumping energy that will be required. In space heating systems with radiant floor/sandbed loops, or in large commercial systems, going up one pipe size can, in some cases, save enough pumping energy to overcome the extra installation costs in just a few years. Oversizing in the case of planning for system expansion is justifiable. In every other case, oversizing has to be done carefully. The extra costs may often be overlooked. It is not just additional cost in pipe, but it is also more costly labor, fittings, and hangers. It carries over to larger insulation and jacketing, more solar fluid, larger expansion tanks, etc. In commercial systems, the difference is many thousands of dollars. This is the cost that must be offset by the benefits: savings in pumping energy and flexibility for future expansion. Add parallel lines together. 8 gpm for a 1” header means the max number of panels linked together should be 8 to ensure 1 gpm per collector. The 8 limitation of maximum collectors linked together is also a function of manifold expansion and contraction. This applies to harp style absorber plate collectors. Connecting more than 8 four foot wide collectors can result in more expansion than the collectors can withstand without harming the absorber plates and possibly the collector frame as well. Refer to the collector manufacturer for specific information about this point. Max of 4 collectors for ¾” header. Long pipe runs may require expansion loops, L-bends, Z-bends or U-bends per 2008 ASHRAE HVAC systems and Equipment 45.11 Expansion tank: Size this properly. Too big is better than too small. Expansion tanks cannot be oversized too large. The expansion tank in a pressurized system must not have any isolation valves between the tank and the collectors. If isolation valves must be used between the expansion tank and the collectors, remove the handles and hang them nearby. Specify heavy -duty tank. Use a solar rated tank. Typically set the expansion tank back-pressure to 3-5 psi below system pressure before pressurizing the system. Expansion tanks can be added together to handle larger systems. The following table offers suggested expansion tank sizing with the following conditions: 50% propylene Glycol, 2500F maximum solar temperature, 30-psig static pressure and a maximum 20 psig pressure rise. This is mentioned because an expansion tank that is too small is a common mistake in designing solar water heating system. System Volume Tank Size Gallons Cubic Fee t Size (inches) Gallons 5 0.67 10 x15 4.5 10 1.34 10 x15 4.5 15 2.01 10 x15 4.5 20 2.67 12.5 x 19 8.5 25 3.34 12.5 x 19 8.5 30 4.01 12.5 x 19 8.5 40 5.35 16 x 21 14 50 6.68 16 x 21 14 60 8.02 16 x 28 20 70 9.36 16 x 28 20 80 10.70 21 x 28 32 100 13.37 21 x 28 32 Always use high quality solar-rated components. Solar thermal systems may operate at higher temperature conditions and are harder on components than hydronic heating systems. Glycol Pressure should be in the mid-range of the gauge. Drain/fill valves should be fitted with gasketed caps to help prevent accidental opening of the valves. System temperature fluctuations are much larger (-30 to +400°F) than hydronic heating systems; leading to larger expansion tanks and considerations for pipe expansion/contraction. Glycol is different than water: Glycol systems leak easier than water-only systems. It is more erosive – debur all copper tubing, use long 90 -degree turns, and leave an appropriate number of pipe diameters before and after components. It has a higher coefficient of expansion – leading to larger expansion tanks. It is more viscous – leading to greater head loss and larger pumps. It has lower heat capacity – leading to higher flow rates and larger pumps. It must be carefully maintained to protect vital system components. It should be tested for freeze protection and PH every five years or whenever the system has encountered a prolonged no-flow situation Use only solar approved and rated glycol fluids Drainback systems Use only type M, L, or K copper pipe; no steel, galvanized, or Pex pipe. Minimum pipe size is ¾” for drainback systems. Do not use galvanized fittings. Use brass or bronze fittings. All cast or steel components must be electronically isolated from all other components in the system. Pipe must be sloped and supported by tubing hangers. To prevent sagging, the hangers should be spaced per MSS SP-69. Nominal Copper Tube Size(Nominal Pipe Size) Maximum Spacing(ft) 1/2 5 3/4 5 1 6 1 1/4 7 1 1/2 8 2 8 2 1/2 9 3 10 On any change in horizontal direction, place a hanger within one foot of the directional change. On vertical runs, support the pipe at least once every ten feet. Install hangers that are large enough to handle the tubing insulation and completely insulate all pipes. Tilt collectors per manufacturers recommendation for drainback systems. Size drainback tanks to hold all the liquid in the collectors and piping above the drainback tank. No vents on or above drainback tanks. Drainback systems are “closed loop.” Size the high head pump for the pipe friction and static head to the top of the solar panels. It is always best to have the pump running as close to the published pressure curve as possible. Err on the side of too much head when choosing the pump. Two pumps or dual speed pumps can be used, one dropping out or switching to a slower speed after flow has been established, using a timer or otherappropriate type of controller that has this function. Install the high head pump a minimum of two feet below the drainback tank. Use pipe insulation on the solar loop that is rated for a minimum continuous temperature of 180 degrees and use pipe insulation rated to at least 250 degrees within 10 feet of the solar collectors. Pipe insulation on the solar loop should be at least an R-4 rating. 1” high temperature foam insulation is generally rated at R-7 and is better. Do not use serpentine flat plate collectors in drainback systems. Do not mount harp-style flat plate collectors in the landscape position in drainback systems Pressurized glycol systems For large systems with lots of exterior piping in cold climates, install a heat exchanger bypass to stop potential heat exchanger freezing. If corrugated piping is used, be sure to consider the friction head of the pipe. Corrugated piping has a high pressure drop/friction head. Adequate pressure in solar loop: in cold climates, a minimum of 35psi is generally required to keep pressure in the system when it gets below zero. The higher the pressure, the higher the boiling point of the solar fluid. Make sure the back-pressure of the expansion tank is set accordingly (3#-5# below system pressure @ 600 F) Some installers use a glycol compatible boiler to stop leaks — this is a good precautionary practice. Add it to the solar fluid to control micro-leaks, which are sometimes found in cast parts. On Photovoltaic (PV) powered systems, use proper wire size between PV and pump or controller. No galvanized pipe or fittings. Sleeve all buried pipes. Hang all fittings below the pipe including expansion tank(s). In freezing weather, cold solar fluid can freeze the heat exchanger on system start-up. Bypass consists of an aquastat which that measures incoming solar fluid temperature. If below a certain temperature, the aquastat engages a motorized valve which diverts the solar fluid back to the collector array. If using a swing check valve, locate the valve properly. There should only be one check valve on the solar loop of a pressurized glycol system. If using a spring check valve, ensure it is the low resistance type. Because all pressurized systems have the potential to “steam-back”, it is considered a best practice to install the check valve on the return piping (going back to the collector) and to locate the expansion tank above the check valve. When a system goes into “steam-back”, steam forms inside the collector and pushes any remaining fluid down through the return line and ending up in the expansion tank. Therefore the expansion tank must not be isolated from the collector on the return line (flow to the collector). Isolate the air vent located at the top of the piping with a ball valve and close after one month of operation. Make sure the automatic air vent is solar rated. Use ball valve-type valves for fill and drain valves and cap with gasketed cap. Be aware of a potential problem with using ball valves on the solar loop. The potential problem is that many ball valves capture a small amount of liquid within the valve body. When the valve is exposed to elevated temperatures, the captured liquid will expand and may damage the plastic seal resulting in a leaky valve. Solar rated ball valves generally are made to eliminate this problem. Use pipe insulation on the solar loop between the collector array and the heat exchanger that is rated to at least 250°F continuous. 180 degree-rated pipe insulation is adequate on the solar loop piping from the heat exchanger back to the collector array. Use only closed cell foam pipe insulation on all exterior pipes, including all buried pipes. All buried pipes should be placed inside a sleeve or chase and never direct buried which. The chase will allow for expansion and contraction of the pipe and help eliminate pipe failure. Route sensor wire inside a pipe jacket or within a dedicated conduit where it will not be exposed to the elements. Installation – Roof Every roof structure that solar collectors will be mounted on must be carefully inspected for structural integrity. Depending on your location, many permitting authorities will require an in-depth description and possibly an accurate analysis of the load carrying capacity of a roof where solar collectors will be mounted. All non-residential buildings over 50,000 cubic feet that will have solar collectors mounted on them will require a set of approved plans in order to receive a building permit. Document the construction of the roof. Most municipalities will require structural information about buildings where solar collectors will be mounted on them in order to receive a building permit. The more information you can collect about the structure of the building will help facilitate this process. Some municipalities will require calculations to show that the weight loading of the solar collector array will not adversely affect the building structure. At a minimum, the following information/documentation about (and photos of) the building will be needed: If the collectors will be mounted on a rail system (recommended), attach the rails to every rafter or truss to distribute the load evenly on the maximum number of framing members. Size of framing members (2×4, 2×6, etc.). Measure all spans (span of roof members) as well as the width, depth, and height of the building. Document if the roof structure uses trusses or rafters. For trusses, measure and draw a diagram that includes where all truss members and plates are located. For rafters, identify if there are any braces or beams. On the roof drawing, specify exactly where the solar collectors will be located. Include exact locations of all anchor points. If using trusses, get a copy of the truss manufacturer’s specification sheet if possible. Document if and where there are any chimneys, skylights, or dormers on the roof structure. Take photos of the roof structure if accessible (both exterior and interior). Document the type and dimensions of the roof sheathing. Document type and number of layers of shingles and felt. For steel or tiled roofing materials, document the weight of those materials (pounds per square foot). Spread the load over a large area as this reduces point loads on the roof. Use spanner mounting hardware if available or lag bolts as directed specified by a structural engineer or approved by the solar equipment manufacturer, local building authority to secure the solar collectors to the roof. Best Practices: When using lag bolts lag into the exact center of the framing member. Always use the recommended size and type of lag bolt. Ensure each penetration through roof made for the collector mounting hardware is properly flashed in accordance with local building codes. Ensure each penetration through the roof made for solar loop piping is properly flashed in accordance with local building codes. Use butyl type caulk. Use roofing grade caulk that stays flexible forever, that never dries out and sticks to wood, shingles and metal. Do not locate relief valves on the roof. Only used closed-cell, foam, high temperature pipe insulation above the roof. Mineral wool or fiberglass pipe insulation may provide fire protection where the piping passes through a firestop. Jacket all exposed piping. Use stainless steel fasteners. Use solid brass unions between collectors. Do not install collectors on a bad roof. If shingles are nearing the end of their useful life (curling, breaking, or significant loss of aggregate), the building should be re-roofed before the collectors are installed. Installation – Awning Mount Where the collector array is hung on a wall, the wall must be strong enough to hold the weight of the collectors and racking. Distribute the weight over as many building framing members as possible. Unistrut-type racking bolted to the framing members can distribute the weight evenly on the wall. Do not just bolt/screw fasteners into the sheathing alone, bolt/screw into the framing members of the wall. If the wall has a brick veneer, the racking must pass through the veneer to the wall framing members behind the brick. Most flat plate collectors cannot be hung from the top rail of the collector because the collector was not designed to be mounted in this way. To strengthen a flat plate collector so it can be hung from its top rail, install two pieces of aluminum angle iron connecting the top rail to the bottom rail, spaced one foot in from each side. This will hold the collector together. Another method is to install a rack to the wall and then flush mount the collectors to the rack. Installation – General Use water-soluble flux. Rinse solar loop with cold, then hot water until clear (with boiler cleaner added), then follow with a hot then cold water rinse before filling solar loop with solar fluid. This will clean out any dirt, oils and flux residues. Use only “Solar Rated” Propylene Glycol. The temperature rating should be at least 320°F continuous. Check glycol with refractometer after filling to ensure proper freeze protection. Dilute glycol with distilled or de-mineralized water only. If using a water-only drainback, use distilled or de-mineralized water as the solar fluid. Do not use di-electric unions on stainless steel storage tanks. If piping travels down the side of a house, consider using vinyl two-piece chase. Properly seal rim joist penetrations. Installation – Controller Ground collector array and piping with a continuous length of ground cable, no splices. Terminate ground at main electrical panel ground lug. Collectors and solar loop piping must be properly grounded as per NFPA 780 (national standard for lightening protection systems) Use proper size and type of sensor wire. Use jacket sensor wire that is rated for outdoor use Required: twisted wire (#18 minimum) with a shielded cable. Only attach shield to ground lug in controller and trim other end of shield. Use watertight connectors or solder connections. Corroded sensor wire splices are a common problem that can be easily remedied. Utilize a telecommunications splice as an option. Installation – Sensors Use heavy-duty high temperature-rated sensors. The best location for the collector sensor is on top of the upper collector manifold, preferably inside the collector. If sensor is clamped outside of the collector, insulate very well. Where feasible, use immersion wells instead of clamping methods. Use heat transfer grease on all sensors. Securely clamp sensor to collector and/or tank. Installation – Heat Exchanger Install isolation valves and drain/fill ports on the waterside of the heat exchanger to facilitate cleaning, especially if the heat exchanger is the plate type. Remove the handles on the isolation valves so they will not inadvertently be closed. Hang the handles nearby. Insulate heat exchanger well. Label the heat exchanger (single or double wall). Installation – Potable Side of System Use a domestic water thermal expansion tank where there is a backflow preventer on the cold -water inlet. Common applications are commercial buildings and well systems (often the well tank is not sized to accommodate extra expansion, especially in large systems) .). Place the expansion tank so there is not a check valve between the storage tanks and the expansion tank. DHW recirculation systems: There are as many domestic hot water recirculation systems as there are buildings. There is no specific recommended DHW recirculation system recommended for use when a solar water heating system is present. It is important that if there is a DHW recirculation system present that certain precautions be observed. The following are some concepts to keep in mind: Route the recirculation return so it 1) bypasses the solar storage tank and returns to the backup water heater, or 2) can be diverted to either the solar storage tank (when it is warmer than the recirculating return) or the backup water heater using automatic controls. Routing the recirculating return to go through the solar storage tanks all of the time sets a minimum tank temperature of at least 100°F, thereby increasing standby losses and decreasing solar contribution. Install a check valve on the cold -water inlet to the thermostatic mixing valve to reduce thermosiphoning of heat up the cold -water inlet. Check valves may be necessary on other ports of the thermostatic mixing valve if the system has recirculation present. In cases where the mixing valve is set to a lower temperature than the backup water heater, the DHW recirculation return should branch through the backup water heater and the thermostatic mixing valve. DHW Recirculation systems should not be used with one-tank systems. Indoor Swimming Pool Heating Systems Cuprous-Nickel or marine-grade stainless steel (the stainless steel is longer lasting) heat exchangers are required wherever chlorinated pool water may contact the heat exchanger. For salt-water pools a titanium heat exchanger is required. All piping on the pool waterside of the heat exchanger should be plastic. When sizing a solar pool heating system for indoor pools, it is considered a best practice to size the collector array to heat the pool 100% on the best solar day of the year and also to tilt the collectors to an angle equal to the latitude of the location plus 15 degrees. This sizing method will maximize the return on investment and minimize any potential overheating during the warm part of the year. The deployment of a seasonal pool heating system on a year-round pool may offer a lower up-front cost, but in return the system provides lower annual energy savings and requires regular and strict adherence to a maintenance schedule (de-commissioning in the Fall and re-commissioning in late Spring). Commissioning Labeling – label major system components. Also label solar loop piping (identify pipes with direction of flow). Heat Exchanger – label stating single or double wall. Glycol label should include: Glycol Manufacturer Date of fill Concentration Refractometer reading System volume Owners Manual should contain: Date of installation System diagram System verbal description Maintenance information, monthly, annually Component warranty information Glycol information Installation and service contractor contact information Want more expert instruction in solar hot water? Enroll in Bob’s Solar Hot Water Design & Installation training, or check out his free History of Solar Thermal in the United States course. Solar Solar Sales & Marketing Solar Thermal Originally posted on September 27, 2013 Written by Bob Ramlow Bob is an ISPQ Emeritus Master Trainer with more than 30 years experience designing and installing solar systems and has been a driving force in the growth of solar thermal use. Bob is co-owner of Artha Sustainable Living Center LLC and the author of 'Solar Water Heating', A Comprehensive Guide to Solar Water and Space Heating Systems, the first book of it's kind written in over 25 years. Bob not only consults and educates on renewable energy, he leads by example living in a home that is powered by the sun and built with sustainable materials. More posts by Bob